Product

“DCU-500” - Intelligent Device Tester

  • peculiarity/
  • function/
  • parameter
  • ■  MU calibrating mode: It can calibrate merging unit (MU) based on current input type and FT3 data input type.

    ■  ECT/EVT calibrating mode: It can calibrate electronic current/voltage transformerECT/EVTbased on IEC61850-9-1,9-2, 9-2LE, IEC60044-7/8 FT3,FT3LE data format.

    ■  6-phase synchronous sampling and simultaneous checkout: It can simultaneously check out 6-phase voltage&current channel. Synchronous sampling of 6 channels ensure the definitely synchronous waveform of every phases and visual data display, including displaying standard, calibrated waveform, differential,angle difference and composite error, discrete type message waveform, harmonic waveform and MU full access waveform. This can chronically observe ECT/EVT or MU linearity and stability.

    ■  Multiple optical port input: The dual-channel IEC61850&IEC60044 data interface and two synchronous clock input&output interface can simultaneously receipt two MU or EIT output to get nuclear phase calculation about relative channel.

    ■   Automatic configuration: Supporting the SCD file import, it can automatically identify MU channel information and configurate relative standard access to channels.

    ■  Multiple timing pattern: Synchronous clock includes IEEE1588, IRIG-B code and second impulse PPS etc. Flexible configuration.

    ■  Operating&controlling by laptop: To test with circumscribed laptop. Powerful functions, convenient operation. Automatic storage of testing results.

     

  • ■  To calibrate electronic transformerECT/EVTwith standard IEC61850(-9-1-9-2-9-2LE).

    ■  To calibrate electronic transformerECT/EVTwith standard IEC60044(FT3FT3LE).

    ■  To calibrate merging unitMUwith standard IEC61850(-9-1-9-2-9-2LE).

    ■  To calibrate merging unitMUwith standard IEC60044(FT3FT3LE).

    ■  To calibrate merging unitMUwith standard voltage, current analog input.

    ■  Self-prepared 0~120V with class 0.05, using 0~6A precised three-phase supply to test ( no need for voltage&current booster)

    ■  To calibrate electronic transformer polarity, delay and message shake.

    ■  To get nuclear calculation for digital signal came from the same or different MU or ECT/EVT.

    ■  To simultaneously calibrate three-phase voltage&current, it can display voltage & current phase angle, active and reactive power etc.

     

  • ■  voltage: 0~120V

    ■  current: 0~6A

    ■  Precision: class 0.05 ( differential <0.05%, angle difference <2’
     Input voltage&current measurement

    ■  Precision: class 0.05 ( differential <0.05%, angle difference <2’
     Communication protocol

    ■  IEC61850-9-1-9-2-9-2LE IEC60044 FT3FT3LE
    Input signal limits

    ■  voltage: 0~120V

    ■  current: 0~6A
    Harmonic testing precision

    ■  Differential: 0.1%Uh or 0.1%Ih, angle difference 10’ waveform discrete characteristics test

    ■  precision: <0.1us
    Digital input interface

    ■  IEC618502 pairs ST interface ( multimode optical fiber, wavelength 1310nm

    ■  IEC6185442 pairs ST interface ( multimode optical fiber, wavelength 1310nm

    Timing system

    ■  Input: IRIG-B code, PPS second impulse   2 pairs ST interface, multiplexing, can be set 

        IEEE1588, 2 pairs ( multiplexing with IEC61850 input interface, can be set)

    ■ Output:IRIG-B code, PPS second impulse   2 pairs ST interface, multiplexing, can be set 

     

© 2014 wuhan haomai electric power automation technology co., LTD/wuhan haomai photoelectric technology co.,
LTD ALL RIGHTS RESERVED
Hubei ICP for 05010718-1 Technical support;Hubei baijie   Halma's official weibo

24 hours service hotline13971234137

hotline400-099-8859