Product

“CTP-200” - Transformer Comprehensive Tester (frequency conversion, class 0.05)

  • peculiarity/
  • function/
  • parameter
  •     Testing CT/PT VA characteristics curve and 10% error curve based on advanced frequency variation method, it outputs only 180V AC voltage and 5A AC current when it gets the most. But this can handle the CT test when its inflection point gets up to 30KV.
     
        All-sized functions, it can be used in steady or transient state characteristic testing, such as excitation with every kinds of CT&PT types, transformation ratio, phase, polarity, secondary winding resistance, load, differential and angle difference.
     
        It will automatically give the parameters of inflection point voltage/current, 10% error curve, 5% error curve, ALF, FS, Ts, Kr, accuracy class, saturable and unsaturated inductance etc.
     
        Ability to test and calculate CT&PT according to different standards of GB1208-2006 (IEC60044-1), GB16847-1997 (IEC60044-6) etc.
     
        Beautiful interface, graphical interface all in Chinese, 6.4 cun LCD, visible in the sunlight.
     
        The device can store 3000 groups of testing data, no loss. And it can load data to analyze after testing, or upload to PC through U disk to generate WORD report.
     
        Convenient testing. The other tests are all based on the same wiring except for loading test.
     
        Easy to take, weight <9Kg.
     
        This product can be used with “CTPS1 large current generator”, it can output 150A current in maximum to carry out spot through-flow test.
  •  Device design can use in the following tests of CT&PT:

     
        Excitation characteristic testing
     
        Transformation ratio test
     
        Phase and polarity test
     
        Differential and angle difference measurements of CT under various primary current and load.
     
        CT secondary winding resistance measurement
     
        CT secondary circuit loading measurement
     
        CT transient state characteristic test and analysis
     
        Test and checkout all kind types of CT&PT, including protection CT, measuring CT, TP-level’s transient state CT, CT with excitation saturable voltage getting up to 30KV, transformer drivepipe CT and PT with various voltage class.
     
         Parameters measurement of CT&PT,such as inflection point voltage/current, 10% (5%) error curve, ALF, FS, Ts, Kr, accuracy class, saturable and unsaturated inductance etc. 
  •     Output voltage: 0~180V (RMS)
     
        Output current: 0~5A, peak value 15A
     
        Voltage measuring: accuracy rating ±0.1%
     
        CT transformation ratio measuring range: 1~10000
     
        PT transformation ratio measuring range: 1~10000
     
        Transformation ratio measurement: accuracy rating ±0.05%
     
        Phase measuring: accuracy rating ±3’, resolution ratio 0.3’
     
        Secondary winding resistance measuring range: 0.1~300Ω, resolution ratio 0.2mΩ, precision 1%±1 mΩ.
     
        AC loading measurement: 0~300VA, accuracy 1%±0.1VA
     
        Input supply voltage: AC220V±20%, 50HZ
     
        Working conditions: Temperature -10℃~50℃, humidity ≤90%
     
        Size: 340mm×300mm×150mm
     
        Weight: <9kg
     
        This product can be used with “CTPS1 large current generator”, it can output 150A current in maximum to carry out spot through-flow test.
© 2014 wuhan haomai electric power automation technology co., LTD/wuhan haomai photoelectric technology co.,
LTD ALL RIGHTS RESERVED
Hubei ICP for 05010718-1 Technical support;Hubei baijie   Halma's official weibo