Product

"RELAYTESTAR-806"- Relay Protection Testing System

    24小时服务热线:1397 1234 137 / 400 099 8859

  • peculiarity/
  • function/
  • parameter
  • Built-in IPC: Host machine is the high-performance IPC, it can directly operate the Windows XP operating system. It has powerful functions, reliable and stable features.
     
    Convenient stand-alone operation: Here are trackball mouse, optimized keyboard and large screen TFT LCD on the device faceplate, and Windows platform operating software entirely in Chinese. The operation becomes more convenient and efficient.
     
    Dual-operation mode: Built-in IPC, support the stand-alone operation and online operation, completely same function with the two way, that’s the real dual-operation mode.
     
    High-performance host machine: Adopting the latest super-speed DSP control, it has the advantages of top-speed calculating speed, wide transmission band, high-precised output waveform, low distortion, well linearity, strong real-time processing ability and can control high resolution D/A conversion.
     
    Linear power amplifier output: Adopting modular linear power amplifier rather than switch-type power amplifier. It’s of excellent performance, high power, high reliability and low ripple wave interference, so as to ensure the smooth waveform and well precision from large current to small current.
     
    Abundant interfaces: Equipped with USB port and USB communication interface, it’s convenient for data storage and software update. Support the external devices.
     
    Easy test for ATS:10 routes for binary input while 8 routes for binary output, it can test all kinds of ATS and fast cutting devices. The design of testing interface is beautiful, and it can display every kinds of system wiring diagram, contact state of switches and amplitude of current&voltage. Thus, it can intuitively and conveniently test, record and display the whole action process of ATS equipment.
     
    Powerful functions: It can finish all kinds of large-scale and complicated checkout work with high automatic level. This will be convenient to test and scan various protective definite value, to carry out bug playback, to store testing data in the real time, to display vector diagram and to print report online. 6-phase current can conveniently proceed with 3-phase differential motion protective testing, while 12-phase output can be used in ATS testing.
     
        GPS’s control function: It can carry out bilaterally timing synchronous testing and fiber-optical current differential protection testing. 7 routes for current&voltage output, they are Ua, Ub, Uc, Ia, Ib, Ic and the fourth group of voltage Ux output. Ux can used in many functions, for instance, output various 3U0 etc.
     
    Independent DC power supply: Equipped with one-route special DC power supply output of high power 110V or 220V.
     
    Impeccable self-defense function: Reasonable design with heat dissipation structure, reliable and impeccable hardware protective measures. Equipped with soft start function of power supply, fault self-diagnostic function of software and latching function of output.
     
    Integration structure with light&small type: Adopting abundant advanced technology and component materials, with professional structure design, it has the features of small volume, light weight and complete functions. Convenient for flow test.
  •     Except detecting various relay protection testers ( such as current, voltage, IDMT, power direction, impedance, differential, low-cycle, simultaneous, frequency, DC and time etc) and microcomputer protection, it can also simulate instantaneous, permanent and transformational faults to test from single-phase to three-phase. Moreover, it can finish all kinds of large-scale and complicated checkout work with high automatic level. This will also be convenient to test and scan various protective definite value, to carry out bug playback,to store testing data in the real time, to display vector diagram, to print report online and to test ATS, fast cutting and system shock etc.

  •     AC current output: 3 routes, 40A/ 450VA per route
     
        AC voltage output: 4 routes, AC125V / 85VA per route
     
        AC output accuracy: 0.1% (between the main measuring range)
     
        DC current output: 3 routes, ±10A/ 200VA per route
     
        DC voltage output: 4 routes, ±160V (220V/150W) per route
     
        DC output accuracy: 0.2% (between the main measuring range)
     
        Phase:  0~359.9°
     
        Phase accuracy: <0.2°
     
        Output frequency: 0~1200Hz
     
        Frequency accuracy: <0.001Hz
     
        Overlying harmonic wave: 2~24 times 
© 2014 wuhan haomai electric power automation technology co., LTD/wuhan haomai photoelectric technology co.,
LTD ALL RIGHTS RESERVED
Hubei ICP for 05010718-1 Technical support;Hubei baijie   Halma's official weibo

24 hours service hotline13971234137

hotline400-099-8859

Share